  "scope": "Thermal duty comparison for saved radial fault cases",
  "cases": {
    "balanced": {
      "study": "Synthetic constant-RMS I-squared-t screen",
      "fault_bus": "FEEDER-END",
      "equipment_id": "SECONDARY-PHASE",
      "initial_rms_ka": 8.37949613248116,
      "source_fault_sha256": "2dac8d9a3e0f0bc77cd6327a7ad49a94121035501df08eef5bd9698d254b6df5",
      "duty_settings_sha256": "515904ccbc2bee2542ebb22f4aa196af9c0a4c44e515150d6cbd005f515610f4",
      "clearing_seconds": 0.1,
      "screening_ka2_seconds": 7.021595543426672,
      "withstand_ka2_seconds": 1,
      "status": "exceeds_rating",
      "thermal_margin_ka2_seconds": -6.021595543426672,
      "constant_initial_rms_duration_at_rating_s": 0.01424177729712955,
      "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope.",
      "current_basis": "three_phase_rms"
    },
    "ground": {
      "study": "Synthetic constant-RMS I-squared-t screen",
      "fault_bus": "FEEDER-END",
      "equipment_id": "SECONDARY-NEUTRAL",
      "initial_rms_ka": 5.321882292595224,
      "source_fault_sha256": "e80710130abe12b53a6a825296798e02878befe44ea624133819a8f605bd8853",
      "duty_settings_sha256": "7eb087f8887dde769d91c3350e55ccbc93e73f566ebd250840b954853bff8042",
      "clearing_seconds": 0.1,
      "screening_ka2_seconds": 2.83224311362386,
      "withstand_ka2_seconds": 1,
      "status": "exceeds_rating",
      "thermal_margin_ka2_seconds": -1.8322431136238602,
      "constant_initial_rms_duration_at_rating_s": 0.03530770346619356,
      "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope.",
      "current_basis": "ground_return_rms"
    }
  },
  "thermal_utilization_by_case": {
    "balanced": 7.021595543426672,
    "ground": 2.83224311362386
  },
  "source_network_sha256_by_case": {
    "balanced": "ddf66e85acff1712bd3f008a1ec707456ecebfa00cfd2f57454d70fedaec82c1",
    "ground": "5a4fc1b34f55da8d94a9a8f83853b50b5b349debcf79b81ef7dd5261394f42ac"
  },
  "equipment_summary": {
    "SECONDARY-PHASE": {
      "unresolved_cases": [],
      "maximum_thermal_utilization": 7.021595543426672,
      "governing_cases": [
        "balanced"
      ]
    },
    "SECONDARY-NEUTRAL": {
      "unresolved_cases": [],
      "maximum_thermal_utilization": 2.83224311362386,
      "governing_cases": [
        "ground"
      ]
    }
  },
  "unresolved_cases": [],
  "maximum_thermal_utilization": 7.021595543426672,
  "governing_cases": [
    "balanced"
  ],
  "verified_csv_fields": {
    "balanced": {
      "current_basis": "three_phase_rms",
      "initial_rms_ka": "8.37949613248116",
      "source_fault_sha256": "2dac8d9a3e0f0bc77cd6327a7ad49a94121035501df08eef5bd9698d254b6df5"
    },
    "ground": {
      "current_basis": "ground_return_rms",
      "initial_rms_ka": "5.321882292595224",
      "source_fault_sha256": "e80710130abe12b53a6a825296798e02878befe44ea624133819a8f605bd8853"
    }
  }
}