  "release_sha256": "56c689d8dda8b9064b7969c6c6d69f0bc825d27c6db6507dacc302c1818f5559",
  "project": {
    "version": 2,
    "name": "Synthetic data center backup-fed AC island",
    "project_kind": "terminal_drawing",
    "wires": [],
    "ac_network": {
      "base_mva": 1,
      "buses": [
        {
          "id": "B2",
          "number": 3,
          "name": "Transformer secondary",
          "kind": 0,
          "p": 0,
          "q": 0,
          "setpoint": 1,
          "reference_voltage": 1,
          "reference_angle": 0,
          "shunt": [
            0,
            0
          ]
        },
        {
          "id": "B3",
          "number": 4,
          "name": "UPS input / IT aggregate",
          "kind": 0,
          "p": -0.32,
          "q": -0.08,
          "setpoint": 1,
          "reference_voltage": 1,
          "reference_angle": 0,
          "shunt": [
            0,
            0
          ]
        },
        {
          "id": "B4",
          "number": 5,
          "name": "Cooling panel",
          "kind": 0,
          "p": -0.18,
          "q": -0.07,
          "setpoint": 1,
          "reference_voltage": 1,
          "reference_angle": 0,
          "shunt": [
            0,
            0
          ]
        },
        {
          "id": "GEN",
          "number": 6,
          "name": "Backup source",
          "kind": 3,
          "p": 0,
          "q": 0,
          "setpoint": 1,
          "reference_voltage": 1,
          "reference_angle": 0,
          "shunt": [
            0,
            0
          ]
        }
      ],
      "connections": [
        {
          "id": "IT-FEED-FROM",
          "closed": true,
          "from": "IT-FEED:FROM",
          "to": "B2:BUS"
        },
        {
          "id": "IT-FEED-TO",
          "closed": true,
          "from": "IT-FEED:TO",
          "to": "B3:BUS"
        },
        {
          "id": "COOLING-FEED-FROM",
          "closed": true,
          "from": "COOLING-FEED:FROM",
          "to": "B2:BUS"
        },
        {
          "id": "COOLING-FEED-TO",
          "closed": true,
          "from": "COOLING-FEED:TO",
          "to": "B4:BUS"
        },
        {
          "id": "GEN-TIE-FROM",
          "closed": true,
          "from": "GEN-TIE:FROM",
          "to": "GEN:BUS"
        },
        {
          "id": "GEN-TIE-TO",
          "closed": true,
          "from": "GEN-TIE:TO",
          "to": "B2:BUS"
        }
      ],
      "equipment_ids": [
        "IT-FEED",
        "COOLING-FEED",
        "GEN-TIE"
      ]
    },
    "n_1_summarize_islands": true,
    "n_1_solve_islands": true,
    "devices_ids": [
      "service"
    ],
    "equipment_roster": {
      "service": {
        "scope": "control",
        "record": {
          "id": "service",
          "kind": "utility",
          "sheet": 1,
          "terminals": [
            "L1"
          ]
        }
      },
      "IT-FEED": {
        "scope": "ac",
        "record": {
          "id": "IT-FEED",
          "number": 3,
          "kind": "branch",
          "r_pu": 0.015,
          "x_pu": 0.02,
          "rating_mva": 1,
          "tap": 1,
          "shift_deg": 0,
          "charging_pu": 0
        }
      },
      "COOLING-FEED": {
        "scope": "ac",
        "record": {
          "id": "COOLING-FEED",
          "number": 4,
          "kind": "branch",
          "r_pu": 0.025,
          "x_pu": 0.025,
          "rating_mva": 1,
          "tap": 1,
          "shift_deg": 0,
          "charging_pu": 0
        }
      },
      "GEN-TIE": {
        "scope": "ac",
        "record": {
          "id": "GEN-TIE",
          "number": 5,
          "kind": "branch",
          "r_pu": 0.002,
          "x_pu": 0.012,
          "rating_mva": 0.45,
          "tap": 1,
          "shift_deg": 0,
          "charging_pu": 0
        }
      }
    }
  },
  "normal_tie_rating_mva": 1,
  "reference_source_mva": 0.5269441527268167,
  "reference_voltage_pu": [
    0.9971321093362846,
    0.9906579404219339,
    0.9908203422082523
  ],
  "normal": {
    "study": "balanced AC load flow",
    "base_mva": 1,
    "reference_bus": 6,
    "iterations": 3,
    "max_mismatch_pu": 2.387914006268517e-12,
    "total_branch_loss_mw": 0.0031681241567687035,
    "buses": [
      {
        "id": 3,
        "name": "Transformer secondary",
        "voltage_pu": 0.9971321093363411,
        "angle_deg": -0.32896467597406925,
        "net_mw": 1.1969332126621196e-12,
        "net_mvar": 2.387914006268517e-12,
        "cdf_voltage_error_pu": -0.0028678906636588897,
        "cdf_angle_error_deg": -0.32896467597406925
      },
      {
        "id": 4,
        "name": "UPS input / IT aggregate",
        "voltage_pu": 0.9906579404220293,
        "angle_deg": -0.6305787170803638,
        "net_mw": -0.3199999999990742,
        "net_mvar": -0.07999999999880222,
        "cdf_voltage_error_pu": -0.00934205957797074,
        "cdf_angle_error_deg": -0.6305787170803638
      },
      {
        "id": 5,
        "name": "Cooling panel",
        "voltage_pu": 0.9908203422083397,
        "angle_deg": -0.4884454266338654,
        "net_mw": -0.17999999999939456,
        "net_mvar": -0.06999999999940337,
        "cdf_voltage_error_pu": -0.0091796577916603,
        "cdf_angle_error_deg": -0.4884454266338654
      },
      {
        "id": 6,
        "name": "Backup source",
        "voltage_pu": 1.0,
        "angle_deg": 0.0,
        "net_mw": 0.5031681241540475,
        "net_mvar": 0.15649913394065607,
        "cdf_voltage_error_pu": 0.0,
        "cdf_angle_error_deg": 0.0
      }
    ],
    "branches": [
      {
        "id": 3,
        "from": 3,
        "to": 4,
        "from_mw": 0.32166292516067024,
        "from_mvar": 0.08221723354759697,
        "to_mw": -0.3199999999990742,
        "to_mvar": -0.07999999999880222,
        "loss_mw": 0.0016629251615960516,
        "rating_mva": 1,
        "loading_percent": 33.200408267841986,
        "overloaded": false,
        "equipment_id": "IT-FEED"
      },
      {
        "id": 4,
        "from": 3,
        "to": 5,
        "from_mw": 0.18094985871438943,
        "from_mvar": 0.07094985871439823,
        "to_mw": -0.17999999999939456,
        "to_mvar": -0.06999999999940337,
        "loss_mw": 0.0009498587149948667,
        "rating_mva": 1,
        "loading_percent": 19.436237758463072,
        "overloaded": false,
        "equipment_id": "COOLING-FEED"
      },
      {
        "id": 5,
        "from": 6,
        "to": 3,
        "from_mw": 0.5031681241540475,
        "from_mvar": 0.15649913394065607,
        "to_mw": -0.5026127838738698,
        "to_mvar": -0.15316709225958952,
        "loss_mw": 0.0005553402801777851,
        "rating_mva": 1,
        "loading_percent": 52.694415272292225,
        "overloaded": false,
        "equipment_id": "GEN-TIE"
      }
    ],
    "out_of_service": []
  },
  "restricted": {
    "study": "balanced AC load flow",
    "base_mva": 1,
    "reference_bus": 6,
    "iterations": 3,
    "max_mismatch_pu": 2.387914006268517e-12,
    "total_branch_loss_mw": 0.0031681241567687035,
    "buses": [
      {
        "id": 3,
        "name": "Transformer secondary",
        "voltage_pu": 0.9971321093363411,
        "angle_deg": -0.32896467597406925,
        "net_mw": 1.1969332126621196e-12,
        "net_mvar": 2.387914006268517e-12,
        "cdf_voltage_error_pu": -0.0028678906636588897,
        "cdf_angle_error_deg": -0.32896467597406925
      },
      {
        "id": 4,
        "name": "UPS input / IT aggregate",
        "voltage_pu": 0.9906579404220293,
        "angle_deg": -0.6305787170803638,
        "net_mw": -0.3199999999990742,
        "net_mvar": -0.07999999999880222,
        "cdf_voltage_error_pu": -0.00934205957797074,
        "cdf_angle_error_deg": -0.6305787170803638
      },
      {
        "id": 5,
        "name": "Cooling panel",
        "voltage_pu": 0.9908203422083397,
        "angle_deg": -0.4884454266338654,
        "net_mw": -0.17999999999939456,
        "net_mvar": -0.06999999999940337,
        "cdf_voltage_error_pu": -0.0091796577916603,
        "cdf_angle_error_deg": -0.4884454266338654
      },
      {
        "id": 6,
        "name": "Backup source",
        "voltage_pu": 1.0,
        "angle_deg": 0.0,
        "net_mw": 0.5031681241540475,
        "net_mvar": 0.15649913394065607,
        "cdf_voltage_error_pu": 0.0,
        "cdf_angle_error_deg": 0.0
      }
    ],
    "branches": [
      {
        "id": 3,
        "from": 3,
        "to": 4,
        "from_mw": 0.32166292516067024,
        "from_mvar": 0.08221723354759697,
        "to_mw": -0.3199999999990742,
        "to_mvar": -0.07999999999880222,
        "loss_mw": 0.0016629251615960516,
        "rating_mva": 1,
        "loading_percent": 33.200408267841986,
        "overloaded": false,
        "equipment_id": "IT-FEED"
      },
      {
        "id": 4,
        "from": 3,
        "to": 5,
        "from_mw": 0.18094985871438943,
        "from_mvar": 0.07094985871439823,
        "to_mw": -0.17999999999939456,
        "to_mvar": -0.06999999999940337,
        "loss_mw": 0.0009498587149948667,
        "rating_mva": 1,
        "loading_percent": 19.436237758463072,
        "overloaded": false,
        "equipment_id": "COOLING-FEED"
      },
      {
        "id": 5,
        "from": 6,
        "to": 3,
        "from_mw": 0.5031681241540475,
        "from_mvar": 0.15649913394065607,
        "to_mw": -0.5026127838738698,
        "to_mvar": -0.15316709225958952,
        "loss_mw": 0.0005553402801777851,
        "rating_mva": 0.45,
        "loading_percent": 117.09870060509382,
        "overloaded": true,
        "equipment_id": "GEN-TIE"
      }
    ],
    "out_of_service": []
  }
}