  "release_sha256": "56c689d8dda8b9064b7969c6c6d69f0bc825d27c6db6507dacc302c1818f5559",
  "site_model": false,
  "validation": {
    "valid": true,
    "devices": 1,
    "wires": 0
  },
  "ac": {
    "study": "balanced AC load flow",
    "base_mva": 1,
    "reference_bus": 1,
    "iterations": 3,
    "max_mismatch_pu": 1.4812327230445673e-10,
    "total_branch_loss_mw": 0.0055173723426384935,
    "buses": [
      {
        "id": 1,
        "name": "Utility",
        "voltage_pu": 1.0,
        "angle_deg": 0.0,
        "net_mw": 0.5055173721684874,
        "net_mvar": 0.16944502763891478,
        "cdf_voltage_error_pu": 0.0,
        "cdf_angle_error_deg": 0.0
      },
      {
        "id": 2,
        "name": "Switchboard",
        "voltage_pu": 0.9969720759598902,
        "angle_deg": -0.3291496178566177,
        "net_mw": -8.162115889885999e-12,
        "net_mvar": 3.977058552679177e-11,
        "cdf_voltage_error_pu": -0.003027924040109764,
        "cdf_angle_error_deg": -0.3291496178566177
      },
      {
        "id": 3,
        "name": "Transformer secondary",
        "voltage_pu": 0.9856596289980757,
        "angle_deg": -1.5766699877209693,
        "net_mw": 6.29255520753854e-11,
        "net_mvar": 1.4812327230445673e-10,
        "cdf_voltage_error_pu": -0.014340371001924312,
        "cdf_angle_error_deg": -1.5766699877209693
      },
      {
        "id": 4,
        "name": "UPS input / IT aggregate",
        "voltage_pu": 0.979108763852005,
        "angle_deg": -1.8853938299835857,
        "net_mw": -0.3199999999267322,
        "net_mvar": -0.07999999994831983,
        "cdf_voltage_error_pu": -0.02089123614799504,
        "cdf_angle_error_deg": -1.8853938299835857
      },
      {
        "id": 5,
        "name": "Cooling panel",
        "voltage_pu": 0.9792733452339959,
        "angle_deg": -1.7399093957412202,
        "net_mw": -0.17999999995388316,
        "net_mvar": -0.06999999996805711,
        "cdf_voltage_error_pu": -0.020726654766004105,
        "cdf_angle_error_deg": -1.7399093957412202
      }
    ],
    "branches": [
      {
        "id": 1,
        "from": 1,
        "to": 2,
        "from_mw": 0.5055173721684874,
        "from_mvar": 0.16944502763891478,
        "to_mw": -0.5049488533065759,
        "to_mvar": -0.16603391446744653,
        "loss_mw": 0.000568518861911449,
        "rating_mva": 1,
        "loading_percent": 53.315985497380204,
        "overloaded": false,
        "equipment_id": "SERVICE"
      },
      {
        "id": 2,
        "from": 2,
        "to": 3,
        "from_mw": 0.5049488532984118,
        "from_mvar": 0.16603391450723484,
        "to_mw": -0.5026747778507262,
        "to_mvar": -0.1532422401140041,
        "loss_mw": 0.002274075447685542,
        "rating_mva": 1,
        "loading_percent": 53.15454874363781,
        "overloaded": false,
        "equipment_id": "TX"
      },
      {
        "id": 3,
        "from": 3,
        "to": 4,
        "from_mw": 0.32170238686484826,
        "from_mvar": 0.08226984919914118,
        "to_mw": -0.3199999999267322,
        "to_mvar": -0.07999999994831983,
        "loss_mw": 0.0017023869381160295,
        "rating_mva": 1,
        "loading_percent": 33.20553474976573,
        "overloaded": false,
        "equipment_id": "IT-FEED"
      },
      {
        "id": 4,
        "from": 3,
        "to": 5,
        "from_mw": 0.18097239104880863,
        "from_mvar": 0.07097239106298255,
        "to_mw": -0.17999999995388316,
        "to_mvar": -0.06999999996805711,
        "loss_mw": 0.0009723910949254733,
        "rating_mva": 1,
        "loading_percent": 19.43915806178854,
        "overloaded": false,
        "equipment_id": "COOLING-FEED"
      }
    ],
    "out_of_service": []
  },
  "it_feeder_outage": {
    "outage": {
      "branch": 3,
      "from": 3,
      "to": 4,
      "equipment_id": "IT-FEED"
    },
    "status": "islanded",
    "components": [
      [
        1,
        2,
        3,
        5
      ],
      [
        4
      ]
    ],
    "island_scheduled_injection": [
      {
        "buses": [
          1,
          2,
          3,
          5
        ],
        "reference_buses": [
          1
        ],
        "scheduled_net_mw": -0.18,
        "scheduled_net_mvar": -0.07
      },
      {
        "buses": [
          4
        ],
        "reference_buses": [],
        "scheduled_net_mw": -0.32,
        "scheduled_net_mvar": -0.08
      }
    ],
    "island_ac_studies": [
      {
        "buses": [
          1,
          2,
          3,
          5
        ],
        "reference_buses": [
          1
        ],
        "status": "solved",
        "buses_ac": [
          {
            "id": 1,
            "name": "Utility",
            "voltage_pu": 1.0,
            "angle_deg": 0.0,
            "net_mw": 0.18133812880599365,
            "net_mvar": 0.07313504463429865,
            "cdf_voltage_error_pu": 0.0,
            "cdf_angle_error_deg": 0.0
          },
          {
            "id": 2,
            "name": "Switchboard",
            "voltage_pu": 0.9987617657814132,
            "angle_deg": -0.11644251772759309,
            "net_mw": 2.2202853100190297e-13,
            "net_mvar": 1.4366191451504718e-12,
            "cdf_voltage_error_pu": -0.00123823421858682,
            "cdf_angle_error_deg": -0.11644251772759309
          },
          {
            "id": 3,
            "name": "Transformer secondary",
            "voltage_pu": 0.994064324954086,
            "angle_deg": -0.5536161936142275,
            "net_mw": 1.7363894943047978e-12,
            "net_mvar": 2.794527214320066e-12,
            "cdf_voltage_error_pu": -0.0059356750459139684,
            "cdf_angle_error_deg": -0.5536161936142275
          },
          {
            "id": 5,
            "name": "Cooling panel",
            "voltage_pu": 0.9877328038654881,
            "angle_deg": -0.7140891776348809,
            "net_mw": -0.17999999999797217,
            "net_mvar": -0.06999999999805706,
            "cdf_voltage_error_pu": -0.012267196134511882,
            "cdf_angle_error_deg": -0.7140891776348809
          }
        ],
        "total_branch_loss_mw": 0.0013381288099736377,
        "voltage_violations": [],
        "overloads": [],
        "unrated_branches": []
      },
      {
        "buses": [
          4
        ],
        "reference_buses": [],
        "status": "no_reference"
      }
    ]
  },
  "cooling_feeder_outage": {
    "outage": {
      "branch": 4,
      "from": 3,
      "to": 5,
      "equipment_id": "COOLING-FEED"
    },
    "status": "islanded",
    "components": [
      [
        1,
        2,
        3,
        4
      ],
      [
        5
      ]
    ],
    "island_scheduled_injection": [
      {
        "buses": [
          1,
          2,
          3,
          4
        ],
        "reference_buses": [
          1
        ],
        "scheduled_net_mw": -0.32,
        "scheduled_net_mvar": -0.08
      },
      {
        "buses": [
          5
        ],
        "reference_buses": [],
        "scheduled_net_mw": -0.18,
        "scheduled_net_mvar": -0.07
      }
    ],
    "island_ac_studies": [
      {
        "buses": [
          1,
          2,
          3,
          4
        ],
        "reference_buses": [
          1
        ],
        "status": "solved",
        "buses_ac": [
          {
            "id": 1,
            "name": "Utility",
            "voltage_pu": 1.0,
            "angle_deg": 0.0,
            "net_mw": 0.3228013928008515,
            "net_mvar": 0.08862828985591875,
            "cdf_voltage_error_pu": 0.0,
            "cdf_angle_error_deg": 0.0
          },
          {
            "id": 2,
            "name": "Switchboard",
            "voltage_pu": 0.9982977009478546,
            "angle_deg": -0.21214745757227355,
            "net_mw": 5.980283669715067e-13,
            "net_mvar": 7.534502383058402e-12,
            "cdf_voltage_error_pu": -0.0017022990521453618,
            "cdf_angle_error_deg": -0.21214745757227355
          },
          {
            "id": 3,
            "name": "Transformer secondary",
            "voltage_pu": 0.9918748014151868,
            "angle_deg": -1.0117162463394418,
            "net_mw": 9.53575392936963e-12,
            "net_mvar": 2.048456638425464e-11,
            "cdf_voltage_error_pu": -0.008125198584813198,
            "cdf_angle_error_deg": -1.0117162463394418
          },
          {
            "id": 4,
            "name": "UPS input / IT aggregate",
            "voltage_pu": 0.9853657122422957,
            "angle_deg": -1.3165574879294821,
            "net_mw": -0.31999999998687456,
            "net_mvar": -0.07999999998595181,
            "cdf_voltage_error_pu": -0.014634287757704256,
            "cdf_angle_error_deg": -1.3165574879294821
          }
        ],
        "total_branch_loss_mw": 0.0028013928241081287,
        "voltage_violations": [],
        "overloads": [],
        "unrated_branches": []
      },
      {
        "buses": [
          5
        ],
        "reference_buses": [],
        "status": "no_reference"
      }
    ]
  },
  "all_outages": {
    "study": "AC N-1 branch contingencies",
    "voltage_limits_pu": {
      "minimum": 0.95,
      "maximum": 1.1
    },
    "baseline": {
      "voltage_violations": [],
      "overloads": [],
      "unrated_branches": []
    },
    "scenario_counts": {
      "islanded": 4
    },
    "scenarios": [
      {
        "outage": {
          "branch": 1,
          "from": 1,
          "to": 2,
          "equipment_id": "SERVICE"
        },
        "status": "islanded",
        "components": [
          [
            1
          ],
          [
            2,
            3,
            4,
            5
          ]
        ],
        "island_scheduled_injection": [
          {
            "buses": [
              1
            ],
            "reference_buses": [
              1
            ],
            "scheduled_net_mw": 0.0,
            "scheduled_net_mvar": 0.0
          },
          {
            "buses": [
              2,
              3,
              4,
              5
            ],
            "reference_buses": [],
            "scheduled_net_mw": -0.5,
            "scheduled_net_mvar": -0.15000000000000002
          }
        ],
        "island_ac_studies": [
          {
            "buses": [
              1
            ],
            "reference_buses": [
              1
            ],
            "status": "solved",
            "buses_ac": [
              {
                "id": 1,
                "name": "Utility",
                "voltage_pu": 1.0,
                "angle_deg": 0.0,
                "net_mw": 0.0,
                "net_mvar": 0.0,
                "cdf_voltage_error_pu": 0.0,
                "cdf_angle_error_deg": 0.0
              }
            ],
            "total_branch_loss_mw": 0,
            "voltage_violations": [],
            "overloads": [],
            "unrated_branches": []
          },
          {
            "buses": [
              2,
              3,
              4,
              5
            ],
            "reference_buses": [],
            "status": "no_reference"
          }
        ]
      },
      {
        "outage": {
          "branch": 2,
          "from": 2,
          "to": 3,
          "equipment_id": "TX"
        },
        "status": "islanded",
        "components": [
          [
            1,
            2
          ],
          [
            3,
            4,
            5
          ]
        ],
        "island_scheduled_injection": [
          {
            "buses": [
              1,
              2
            ],
            "reference_buses": [
              1
            ],
            "scheduled_net_mw": 0.0,
            "scheduled_net_mvar": 0.0
          },
          {
            "buses": [
              3,
              4,
              5
            ],
            "reference_buses": [],
            "scheduled_net_mw": -0.5,
            "scheduled_net_mvar": -0.15000000000000002
          }
        ],
        "island_ac_studies": [
          {
            "buses": [
              1,
              2
            ],
            "reference_buses": [
              1
            ],
            "status": "solved",
            "buses_ac": [
              {
                "id": 1,
                "name": "Utility",
                "voltage_pu": 1.0,
                "angle_deg": 0.0,
                "net_mw": 0.0,
                "net_mvar": 0.0,
                "cdf_voltage_error_pu": 0.0,
                "cdf_angle_error_deg": 0.0
              },
              {
                "id": 2,
                "name": "Switchboard",
                "voltage_pu": 1.0,
                "angle_deg": 0.0,
                "net_mw": 0.0,
                "net_mvar": 0.0,
                "cdf_voltage_error_pu": 0.0,
                "cdf_angle_error_deg": 0.0
              }
            ],
            "total_branch_loss_mw": 0.0,
            "voltage_violations": [],
            "overloads": [],
            "unrated_branches": []
          },
          {
            "buses": [
              3,
              4,
              5
            ],
            "reference_buses": [],
            "status": "no_reference"
          }
        ]
      },
      {
        "outage": {
          "branch": 3,
          "from": 3,
          "to": 4,
          "equipment_id": "IT-FEED"
        },
        "status": "islanded",
        "components": [
          [
            1,
            2,
            3,
            5
          ],
          [
            4
          ]
        ],
        "island_scheduled_injection": [
          {
            "buses": [
              1,
              2,
              3,
              5
            ],
            "reference_buses": [
              1
            ],
            "scheduled_net_mw": -0.18,
            "scheduled_net_mvar": -0.07
          },
          {
            "buses": [
              4
            ],
            "reference_buses": [],
            "scheduled_net_mw": -0.32,
            "scheduled_net_mvar": -0.08
          }
        ],
        "island_ac_studies": [
          {
            "buses": [
              1,
              2,
              3,
              5
            ],
            "reference_buses": [
              1
            ],
            "status": "solved",
            "buses_ac": [
              {
                "id": 1,
                "name": "Utility",
                "voltage_pu": 1.0,
                "angle_deg": 0.0,
                "net_mw": 0.18133812880599365,
                "net_mvar": 0.07313504463429865,
                "cdf_voltage_error_pu": 0.0,
                "cdf_angle_error_deg": 0.0
              },
              {
                "id": 2,
                "name": "Switchboard",
                "voltage_pu": 0.9987617657814132,
                "angle_deg": -0.11644251772759309,
                "net_mw": 2.2202853100190297e-13,
                "net_mvar": 1.4366191451504718e-12,
                "cdf_voltage_error_pu": -0.00123823421858682,
                "cdf_angle_error_deg": -0.11644251772759309
              },
              {
                "id": 3,
                "name": "Transformer secondary",
                "voltage_pu": 0.994064324954086,
                "angle_deg": -0.5536161936142275,
                "net_mw": 1.7363894943047978e-12,
                "net_mvar": 2.794527214320066e-12,
                "cdf_voltage_error_pu": -0.0059356750459139684,
                "cdf_angle_error_deg": -0.5536161936142275
              },
              {
                "id": 5,
                "name": "Cooling panel",
                "voltage_pu": 0.9877328038654881,
                "angle_deg": -0.7140891776348809,
                "net_mw": -0.17999999999797217,
                "net_mvar": -0.06999999999805706,
                "cdf_voltage_error_pu": -0.012267196134511882,
                "cdf_angle_error_deg": -0.7140891776348809
              }
            ],
            "total_branch_loss_mw": 0.0013381288099736377,
            "voltage_violations": [],
            "overloads": [],
            "unrated_branches": []
          },
          {
            "buses": [
              4
            ],
            "reference_buses": [],
            "status": "no_reference"
          }
        ]
      },
      {
        "outage": {
          "branch": 4,
          "from": 3,
          "to": 5,
          "equipment_id": "COOLING-FEED"
        },
        "status": "islanded",
        "components": [
          [
            1,
            2,
            3,
            4
          ],
          [
            5
          ]
        ],
        "island_scheduled_injection": [
          {
            "buses": [
              1,
              2,
              3,
              4
            ],
            "reference_buses": [
              1
            ],
            "scheduled_net_mw": -0.32,
            "scheduled_net_mvar": -0.08
          },
          {
            "buses": [
              5
            ],
            "reference_buses": [],
            "scheduled_net_mw": -0.18,
            "scheduled_net_mvar": -0.07
          }
        ],
        "island_ac_studies": [
          {
            "buses": [
              1,
              2,
              3,
              4
            ],
            "reference_buses": [
              1
            ],
            "status": "solved",
            "buses_ac": [
              {
                "id": 1,
                "name": "Utility",
                "voltage_pu": 1.0,
                "angle_deg": 0.0,
                "net_mw": 0.3228013928008515,
                "net_mvar": 0.08862828985591875,
                "cdf_voltage_error_pu": 0.0,
                "cdf_angle_error_deg": 0.0
              },
              {
                "id": 2,
                "name": "Switchboard",
                "voltage_pu": 0.9982977009478546,
                "angle_deg": -0.21214745757227355,
                "net_mw": 5.980283669715067e-13,
                "net_mvar": 7.534502383058402e-12,
                "cdf_voltage_error_pu": -0.0017022990521453618,
                "cdf_angle_error_deg": -0.21214745757227355
              },
              {
                "id": 3,
                "name": "Transformer secondary",
                "voltage_pu": 0.9918748014151868,
                "angle_deg": -1.0117162463394418,
                "net_mw": 9.53575392936963e-12,
                "net_mvar": 2.048456638425464e-11,
                "cdf_voltage_error_pu": -0.008125198584813198,
                "cdf_angle_error_deg": -1.0117162463394418
              },
              {
                "id": 4,
                "name": "UPS input / IT aggregate",
                "voltage_pu": 0.9853657122422957,
                "angle_deg": -1.3165574879294821,
                "net_mw": -0.31999999998687456,
                "net_mvar": -0.07999999998595181,
                "cdf_voltage_error_pu": -0.014634287757704256,
                "cdf_angle_error_deg": -1.3165574879294821
              }
            ],
            "total_branch_loss_mw": 0.0028013928241081287,
            "voltage_violations": [],
            "overloads": [],
            "unrated_branches": []
          },
          {
            "buses": [
              5
            ],
            "reference_buses": [],
            "status": "no_reference"
          }
        ]
      }
    ],
    "ranked_outage_overloads": [],
    "ranked_outage_voltage_violations": [],
    "out_of_service": [],
    "network_sha256": "a76b471921e62088137b45b9eef24fc7c0a9a04835f3deaac7faf5c4eea38332",
    "study_input_sha256": "55ba9f67a2bdc09951a0efdfca9cd1f2fe47775387c52af84bff50e1dbb0bc42"
  },
  "expected_disconnected_load_buses": {
    "SERVICE": [
      4,
      5
    ],
    "TX": [
      4,
      5
    ],
    "IT-FEED": [
      4
    ],
    "COOLING-FEED": [
      5
    ]
  },
  "independent_radial_check": {
    "bus_voltage_pu": {
      "Utility": 1.0,
      "Switchboard": 0.9969720759560747,
      "Transformer secondary": 0.9856596289817714,
      "UPS input / IT aggregate": 0.9791087638333938,
      "Cooling panel": 0.9792733452155776
    },
    "branch_loss_mw": {
      "SERVICE": 0.0005685188624679897,
      "TX": 0.0022740754498719587,
      "IT-FEED": 0.0017023869390438045,
      "COOLING-FEED": 0.0009723910955114056
    },
    "voltage_drop_percent_of_base_by_feeder": {
      "IT-FEED": 0.6550865148377549,
      "COOLING-FEED": 0.6386283766193768
    },
    "demand_mw": 0.5,
    "utility_mw": 0.5055173721684874
  },
  "independent_outage_checks": {
    "it": {
      "served_bus": "Cooling panel",
      "voltage_pu": 0.9877328038650526,
      "loss_mw": 0.0013381288100216798,
      "source_connected_path": [
        "SERVICE",
        "TX",
        "COOLING-FEED"
      ]
    },
    "cooling": {
      "served_bus": "UPS input / IT aggregate",
      "voltage_pu": 0.9853657122394354,
      "loss_mw": 0.002801392824498424,
      "source_connected_path": [
        "SERVICE",
        "TX",
        "IT-FEED"
      ]
    }
  },
  "independent_outage_check": {
    "cooling_voltage_pu": 0.9877328038650526,
    "loss_mw": 0.0013381288100216798,
    "source_connected_path": [
      "SERVICE",
      "TX",
      "COOLING-FEED"
    ]
  }
}