  "scope": "Input handoff and provenance only",
  "source_study": "IEC maximum three-phase bolted fault",
  "source_network_sha256": "2a8ebd7ba70b92590ab700a856aa9b0296b23bf33341b722d384a60c9afc7774",
  "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
  "destination_settings_sha256": "efb88a89887ad051b7002fa5de8693f9ed76c4b66673ee1a7919bffa544a92e4",
  "fault_bus": "FEEDER-END",
  "fault_type": "3ph",
  "transferred": {
    "nominal_voltage_kv": 0.4,
    "bolted_fault_current_ka_rms": 8.962416883591409
  },
  "destination_settings": {
    "source_case_id": "trainer-band"
  },
  "missing_inputs": [
    "method",
    "electrode_configuration",
    "enclosure_mm",
    "conductor_gap_mm",
    "working_distance_mm",
    "clearing_time_basis"
  ],
  "status": "missing_inputs",
  "bolted_fault_duty_reference": {
    "study": "Supplied RMS profile clearing-band I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "9855ca312d3be41ca932a2ea65b82b0d09cf94502d4d6076a3507b1dfe4e50a9",
    "clearing_seconds": 0.16,
    "screening_ka2_seconds": 16.420421034106003,
    "withstand_ka2_seconds": 10.0,
    "status": "exceeds_rating",
    "thermal_margin_ka2_seconds": -6.420421034106003,
    "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
    "scope": "Integrates the supplied RMS profile at clearing bounds evaluated at initial RMS current.",
    "clearing_bounds_seconds": [
      0.08,
      0.16
    ],
    "duty_bounds_ka2_seconds": [
      7.556492134963787,
      16.420421034106003
    ],
    "thermal_limit_reached_at_s": 0.10151260917035787,
    "thermal_crossing_vs_clearing_band": "reached_within_band",
    "asymmetrical_band_rms_screen": {
      "rating_ka_rms": 11.651141948668831,
      "maximum_clearing_window_rms_ka": 11.279432395710623,
      "governing_time_s": 0.12,
      "governing_symmetrical_rms_ka": 11.203021104489261,
      "governing_dc_component_ka": 1.3106919171851625,
      "status": "below_rating",
      "scope": "Quadrature of supplied symmetrical RMS and DC RMS over a trailing window",
      "dc_rms_window_s": 0.04
    }
  },
  "duty_reference_scope": "Bolted-fault screen only. Arcing-current clearing time requires a separate assessment.",
  "study_input_sha256": "cb9d08bcfa24b2184477f0ac0942e9af42bf547d8039ce95ac031e771eb0a8dd",
  "handoff_input_sha256": "88a58b8f5012947f4060fc68c3114cf6c332f882ef130c48f0c639b1b630dd1b"
}