  "study": "IEC maximum three-phase bolted fault",
  "fault_location": "FEEDER-END",
  "initial_symmetrical_rms_ka": 8.962416883591409,
  "transformer_correction": 1.0091777437170488,
  "fault_path_r_x_ohm": [
    0.021684735008138067,
    0.018253107857361464
  ],
  "scope": "Single external source, nominal-ratio non-unit transformer and series feeder",
  "equipment_path": [
    "U1",
    "T1",
    "F1"
  ],
  "project_wire_basis": {
    "source_network_sha256": "2a8ebd7ba70b92590ab700a856aa9b0296b23bf33341b722d384a60c9afc7774",
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "connections": [
      {
        "id": "QET-F1-W1",
        "from": "HV:BUS",
        "to": "T1:PRI",
        "closed": true
      }
    ]
  }
}