  "scope": "Input handoff and provenance only",
  "source_study": "IEC maximum bolted fault",
  "source_network_sha256": "a217ba7eef11ed7c69a42a3c9f10a675626f68876a760bef90fad2232e520d70",
  "source_fault_sha256": "02d682060783a0a4339f4fe20299feca6d21670fab73505ab4b20c8e5932ec3a",
  "destination_settings_sha256": "7acfa6eaa4d0da1ba209bc504330ca2991fe2b96a75879847631a63b0e483a22",
  "fault_bus": "FAULT",
  "fault_type": "3ph",
  "transferred": {
    "nominal_voltage_kv": 20,
    "bolted_fault_current_ka_rms": 5.6415374480783145
  },
  "destination_settings": {
    "source_case_id": "low-voltage"
  },
  "missing_inputs": [
    "method",
    "electrode_configuration",
    "enclosure_mm",
    "conductor_gap_mm",
    "working_distance_mm",
    "clearing_time_basis"
  ],
  "status": "missing_inputs",
  "bolted_fault_duty_reference": {
    "study": "Supplied RMS profile clearing-band I-squared-t screen",
    "fault_bus": "FAULT",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 5.6415374480783145,
    "source_fault_sha256": "02d682060783a0a4339f4fe20299feca6d21670fab73505ab4b20c8e5932ec3a",
    "duty_settings_sha256": "8c68598864c583057a7f395587b0154313a2ff92dc8c889c6c9e9a05a122045c",
    "clearing_seconds": 0.1,
    "screening_ka2_seconds": 7.903691286554046,
    "withstand_ka2_seconds": 10.0,
    "status": "below_rating",
    "thermal_margin_ka2_seconds": 2.0963087134459544,
    "constant_initial_rms_duration_at_rating_s": 0.3141991815340816,
    "scope": "Integrates the supplied RMS profile at clearing bounds evaluated at initial RMS current.",
    "clearing_bounds_seconds": [
      0.05,
      0.1
    ],
    "duty_bounds_ka2_seconds": [
      2.7931459349504117,
      7.903691286554046
    ],
    "thermal_crossing_vs_clearing_band": "not_reached_by_latest",
    "interrupting_band_rms_screen": {
      "rating_ka": 8.462306172117472,
      "maximum_clearing_window_rms_ka": 11.283074896156629,
      "governing_time_s": 0.08,
      "status": "exceeds_rating",
      "scope": "Supplied symmetrical RMS over the modeled clearing window"
    },
    "asymmetrical_band_rms_screen": {
      "rating_ka_rms": 11.283074896156629,
      "maximum_clearing_window_rms_ka": 11.564321356715249,
      "governing_time_s": 0.08,
      "governing_symmetrical_rms_ka": 11.283074896156629,
      "governing_dc_component_ka": 2.534906177573543,
      "status": "exceeds_rating",
      "scope": "Quadrature of supplied symmetrical RMS and instantaneous decaying DC offset"
    }
  },
  "duty_reference_scope": "Bolted-fault screen only. Arcing-current clearing time requires a separate assessment.",
  "study_input_sha256": "de7c4c4c9f8c967ece7ab763cb2913ae353396aed6c164e0429d268ba3c0d97b",
  "handoff_input_sha256": "f09b9bdafa38faa7577801c3ea0ba3438460aab59256d96e6d8384db9707dd6a",
  "source_case_id": "low-voltage"
}