  "release_sha256": "56c689d8dda8b9064b7969c6c6d69f0bc825d27c6db6507dacc302c1818f5559",
  "original_withstand_ka": 10,
  "new_withstand_ka": 12.5,
  "unchanged_reports": [
    "panel-schedule",
    "voltage-drop"
  ],
  "changed_duty": {
    "study": "Synthetic constant-RMS I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "7081fe97102da5a2fa70a923113cd134aa36ed6a7f585e0cde72cfc6f7e307b0",
    "clearing_seconds": 0.07967639790006337,
    "screening_ka2_seconds": 6.3999999999999995,
    "withstand_ka2_seconds": 15.625,
    "status": "below_rating",
    "thermal_margin_ka2_seconds": 9.225000000000001,
    "constant_initial_rms_duration_at_rating_s": 0.1945224558107016,
    "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
  },
  "changed_handoff": {
    "scope": "Input handoff and provenance only",
    "source_study": "IEC maximum three-phase bolted fault",
    "source_network_sha256": "d6f6fc1ac3ddfd79ba8c6ac778061e7875d65599568833f0c713451793938118",
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "destination_settings_sha256": "44136fa355b3678a1146ad16f7e8649e94fb4fc21fe77e8310c060f61caaff8a",
    "fault_bus": "FEEDER-END",
    "fault_type": "3ph",
    "transferred": {
      "nominal_voltage_kv": 0.4,
      "bolted_fault_current_ka_rms": 8.962416883591409
    },
    "destination_settings": {},
    "missing_inputs": [
      "method",
      "electrode_configuration",
      "enclosure_mm",
      "conductor_gap_mm",
      "working_distance_mm",
      "clearing_time_basis"
    ],
    "status": "missing_inputs",
    "bolted_fault_duty_reference": {
      "study": "Synthetic constant-RMS I-squared-t screen",
      "fault_bus": "FEEDER-END",
      "equipment_id": "DUTY-LOW",
      "initial_rms_ka": 8.962416883591409,
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "7081fe97102da5a2fa70a923113cd134aa36ed6a7f585e0cde72cfc6f7e307b0",
      "clearing_seconds": 0.07967639790006337,
      "screening_ka2_seconds": 6.3999999999999995,
      "withstand_ka2_seconds": 15.625,
      "status": "below_rating",
      "thermal_margin_ka2_seconds": 9.225000000000001,
      "constant_initial_rms_duration_at_rating_s": 0.1945224558107016,
      "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
    },
    "duty_reference_scope": "Bolted-fault screen only. Arcing-current clearing time requires a separate assessment.",
    "study_input_sha256": "96ee65ae8961626728720323604b0e71b62d4aaf8acd7201c99606666a95fc94",
    "handoff_input_sha256": "7f986ecfe192e728fbea863b7d349e17f520b181880cb3c27aa1fa80229bf9fc"
  }
}