  "release_sha256": "56c689d8dda8b9064b7969c6c6d69f0bc825d27c6db6507dacc302c1818f5559",
  "project": {
    "version": 2,
    "project_kind": "terminal_drawing",
    "name": "Synthetic panel and protection handoff example",
    "wires": [
      {
        "id": "W01",
        "from": "Q1:T1",
        "to": "M1:L1"
      }
    ],
    "voltage_drop": {
      "voltage_v": 208,
      "length_km": 0.1,
      "cases": [
        {
          "case": "running",
          "current_a": 40,
          "coefficient_v_per_a_km": 1,
          "upstream_drop_v": 0,
          "limit_percent": 3
        },
        {
          "case": "starting",
          "current_a": 100,
          "coefficient_v_per_a_km": 1,
          "upstream_drop_v": 0,
          "limit_percent": 8
        }
      ]
    },
    "panel": {
      "id": "PANEL",
      "slots": 72,
      "circuits": [
        {
          "id": "C1",
          "label": "Power supply",
          "slot": 1,
          "phases": [
            "A"
          ],
          "va": 100
        },
        {
          "id": "C2",
          "label": "Fan",
          "slot": 2,
          "phases": [
            "B"
          ],
          "va": 200
        },
        {
          "id": "C3",
          "label": "Heater",
          "slot": 3,
          "phases": [
            "C"
          ],
          "va": 300
        }
      ]
    },
    "iec_network": {
      "buses": [
        {
          "id": "HV",
          "nominal_kv": 20
        },
        {
          "id": "LV",
          "nominal_kv": 0.4
        },
        {
          "id": "FEEDER-END",
          "nominal_kv": 0.4
        }
      ],
      "fault_bus": "FEEDER-END",
      "voltage_factor": 1.1,
      "connections": [
        {
          "id": "PW01",
          "from": "U1:OUT",
          "to": "HV:BUS",
          "closed": true
        },
        {
          "id": "PW02",
          "from": "HV:BUS",
          "to": "T1:PRI",
          "closed": true
        },
        {
          "id": "PW03",
          "from": "T1:SEC",
          "to": "LV:BUS",
          "closed": true
        },
        {
          "id": "PW04",
          "from": "LV:BUS",
          "to": "F1:IN",
          "closed": true
        },
        {
          "id": "PW05",
          "from": "F1:OUT",
          "to": "FEEDER-END:BUS",
          "closed": true
        }
      ],
      "duty_ratings": [
        {
          "id": "DUTY-LOW",
          "bus": "FEEDER-END",
          "initial_rms_ka": 8,
          "peak_ka": 13
        },
        {
          "id": "DUTY-HIGH",
          "bus": "FEEDER-END",
          "initial_rms_ka": 10,
          "peak_ka": 16
        },
        {
          "id": "DUTY-PARTIAL",
          "bus": "FEEDER-END",
          "initial_rms_ka": 9
        }
      ],
      "equipment_ids": [
        "U1",
        "T1",
        "F1"
      ]
    },
    "time_duty": {
      "bus": "FEEDER-END",
      "equipment_id": "DUTY-LOW",
      "clearing_curve": [
        [
          4,
          0.4
        ],
        [
          16,
          0.025
        ]
      ],
      "withstand_seconds": 0.1,
      "withstand_ka": 10
    },
    "devices_ids": [
      "PANEL",
      "Q1",
      "M1"
    ],
    "equipment_roster": {
      "PANEL": {
        "scope": "control",
        "record": {
          "id": "PANEL",
          "kind": "panel",
          "sheet": 1,
          "terminals": [
            "A",
            "B",
            "C",
            "N"
          ]
        }
      },
      "Q1": {
        "scope": "control",
        "record": {
          "id": "Q1",
          "kind": "terminal_block",
          "sheet": 1,
          "terminals": [
            "T1"
          ]
        }
      },
      "M1": {
        "scope": "control",
        "record": {
          "id": "M1",
          "kind": "terminal_block",
          "sheet": 1,
          "terminals": [
            "L1"
          ]
        }
      },
      "U1": {
        "scope": "iec",
        "record": {
          "id": "U1",
          "kind": "utility",
          "short_circuit_mva": 250,
          "r_over_x": 0.1
        }
      },
      "T1": {
        "scope": "iec",
        "record": {
          "id": "T1",
          "kind": "transformer",
          "rated_mva": 1,
          "rated_primary_kv": 20,
          "rated_secondary_kv": 0.4,
          "vk_percent": 6,
          "vkr_percent": 1
        }
      },
      "F1": {
        "scope": "iec",
        "record": {
          "id": "F1",
          "kind": "feeder",
          "length_km": 0.1,
          "r_ohm_per_km": 0.2,
          "x_ohm_per_km": 0.08
        }
      }
    }
  },
  "reports": {
    "validate": {
      "valid": true,
      "devices": 3,
      "wires": 1
    },
    "panel-schedule": {
      "study": "Panel schedule",
      "panel_id": "PANEL",
      "circuits": [
        {
          "id": "C1",
          "slots": [
            1
          ],
          "phases": [
            "A"
          ],
          "connected_va": 100,
          "demand_va": 100
        },
        {
          "id": "C2",
          "slots": [
            2
          ],
          "phases": [
            "B"
          ],
          "connected_va": 200,
          "demand_va": 200
        },
        {
          "id": "C3",
          "slots": [
            3
          ],
          "phases": [
            "C"
          ],
          "connected_va": 300,
          "demand_va": 300
        }
      ],
      "phase_connected_va": {
        "A": 100.0,
        "B": 200.0,
        "C": 300.0
      },
      "phase_demand_va": {
        "A": 100.0,
        "B": 200.0,
        "C": 300.0
      },
      "total_connected_va": 600.0,
      "total_demand_va": 600.0,
      "scope": "Multipole loads are split equally across declared phases."
    },
    "voltage-drop": {
      "scope": "Supplied balanced feeder coefficients and upstream voltage drops",
      "cases": [
        {
          "case": "running",
          "feeder_drop_v": 4.0,
          "total_drop_v": 4.0,
          "drop_percent": 1.9230769230769231,
          "limit_percent": 3,
          "within_limit": true
        },
        {
          "case": "starting",
          "feeder_drop_v": 10.0,
          "total_drop_v": 10.0,
          "drop_percent": 4.8076923076923075,
          "limit_percent": 8,
          "within_limit": true
        }
      ]
    },
    "iec-fault": {
      "study": "IEC maximum three-phase bolted fault",
      "fault_location": "FEEDER-END",
      "initial_symmetrical_rms_ka": 8.962416883591409,
      "transformer_correction": 1.0091777437170488,
      "fault_path_r_x_ohm": [
        0.021684735008138067,
        0.018253107857361464
      ],
      "scope": "Single external source, nominal-ratio non-unit transformer and series feeder",
      "equipment_path": [
        "U1",
        "T1",
        "F1"
      ]
    },
    "time-duty": {
      "study": "Synthetic constant-RMS I-squared-t screen",
      "fault_bus": "FEEDER-END",
      "equipment_id": "DUTY-LOW",
      "initial_rms_ka": 8.962416883591409,
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "9ef15e3a8d2026e1a5275642814438d4b610c665af102fd496273f8345bf0a34",
      "clearing_seconds": 0.07967639790006337,
      "screening_ka2_seconds": 6.3999999999999995,
      "withstand_ka2_seconds": 10.0,
      "status": "below_rating",
      "thermal_margin_ka2_seconds": 3.6000000000000005,
      "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
      "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
    },
    "arc-handoff": {
      "scope": "Input handoff and provenance only",
      "source_study": "IEC maximum three-phase bolted fault",
      "source_network_sha256": "d6f6fc1ac3ddfd79ba8c6ac778061e7875d65599568833f0c713451793938118",
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "destination_settings_sha256": "44136fa355b3678a1146ad16f7e8649e94fb4fc21fe77e8310c060f61caaff8a",
      "fault_bus": "FEEDER-END",
      "fault_type": "3ph",
      "transferred": {
        "nominal_voltage_kv": 0.4,
        "bolted_fault_current_ka_rms": 8.962416883591409
      },
      "destination_settings": {},
      "missing_inputs": [
        "method",
        "electrode_configuration",
        "enclosure_mm",
        "conductor_gap_mm",
        "working_distance_mm",
        "clearing_time_basis"
      ],
      "status": "missing_inputs",
      "bolted_fault_duty_reference": {
        "study": "Synthetic constant-RMS I-squared-t screen",
        "fault_bus": "FEEDER-END",
        "equipment_id": "DUTY-LOW",
        "initial_rms_ka": 8.962416883591409,
        "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
        "duty_settings_sha256": "9ef15e3a8d2026e1a5275642814438d4b610c665af102fd496273f8345bf0a34",
        "clearing_seconds": 0.07967639790006337,
        "screening_ka2_seconds": 6.3999999999999995,
        "withstand_ka2_seconds": 10.0,
        "status": "below_rating",
        "thermal_margin_ka2_seconds": 3.6000000000000005,
        "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
        "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
      },
      "duty_reference_scope": "Bolted-fault screen only. Arcing-current clearing time requires a separate assessment.",
      "study_input_sha256": "96ee65ae8961626728720323604b0e71b62d4aaf8acd7201c99606666a95fc94",
      "handoff_input_sha256": "e4b586ce53b4f6121adcfcbf826d24287e7a68364f93c90e22a9407b481ee9a2"
    }
  },
  "scope": "Synthetic IEC model supplied separately from the terminal wiring."
}