  "passed": true,
  "load_flow_cases": [
    {
      "study": "Physical DC constant-power feeder",
      "load_w": 0,
      "maximum_load_w": 7812.5,
      "voltage_v": 125.0,
      "current_a": 0.0,
      "line_loss_w": 0.0,
      "source_power_w": 0.0,
      "alerts": []
    },
    {
      "study": "Physical DC constant-power feeder",
      "load_w": 1500,
      "maximum_load_w": 7812.5,
      "voltage_v": 118.68051263561058,
      "current_a": 12.638974728778841,
      "line_loss_w": 79.87184109735509,
      "source_power_w": 1579.8718410973552,
      "alerts": []
    },
    {
      "study": "Physical DC constant-power feeder",
      "load_w": 3500,
      "maximum_load_w": 7812.5,
      "voltage_v": 108.93543905251678,
      "current_a": 32.129121894966445,
      "line_loss_w": 516.1402368708061,
      "source_power_w": 4016.140236870806,
      "alerts": [
        "overcurrent",
        "undervoltage"
      ]
    },
    {
      "study": "Physical DC constant-power feeder",
      "load_w": 8000,
      "maximum_load_w": 7812.5,
      "voltage_v": null,
      "current_a": null,
      "line_loss_w": null,
      "alerts": [
        "no_equilibrium"
      ]
    }
  ],
  "fault": {
    "study": "Series RL bolted DC fault",
    "time_constant_s": 0.02,
    "steady_current_a": 500.0,
    "samples": [
      {
        "seconds": 0,
        "current_a": -0.0
      },
      {
        "seconds": 0.005,
        "current_a": 110.59960846429756
      },
      {
        "seconds": 0.02,
        "current_a": 316.06027941427885
      },
      {
        "seconds": 0.04,
        "current_a": 432.33235838169367
      },
      {
        "seconds": 0.1,
        "current_a": 496.63102650045727
      }
    ],
    "scope": "Fixed voltage, zero initial current, no source or interruption dynamics."
  },
  "voltage_and_power_tolerance": 1e-08,
  "fault_current_tolerance_a": 1e-06
}