  "scope": "Ideal sinusoidal voltage and first-cycle flux screen",
  "study_input_sha256": "82427dc19ee50beb1fb2a63d00d5f19388ea05d8a5fa078679e8b774c85af455",
  "cycle_seconds": 0.016666666666666666,
  "knee_flux_pu": 2,
  "cases": [
    {
      "closing_angle_deg": 90,
      "minimum_flux_pu": -0.9999999999999999,
      "maximum_flux_pu": 1.0,
      "peak_flux_pu": 1.0,
      "knee_exceeded": false,
      "above_knee_seconds": 0.0,
      "peak_magnetizing_current_a": 29.999999999999996,
      "first_cycle_rms_magnetizing_current_a": 15.811388300841896,
      "first_cycle_mean_current_a": -6.366198347854235,
      "first_cycle_harmonic_rms_a": {
        "1": 14.142135623730951,
        "2": 3.001053504468035,
        "3": 2.378796767313689e-16,
        "5": 1.449085090218289e-16,
        "7": 9.639170570866487e-16
      },
      "rms_sample_count": 4096
    }
  ]
}