  "reference_fifth_rms_a": 0.38984840061683795,
  "report": {
    "scope": "Ideal sinusoidal voltage and first-cycle flux screen",
    "study_input_sha256": "224806630ed6ff186c4bb38ef615c3aa8cfb9ccd1ef582f5bd887ca8be5022fd",
    "cycle_seconds": 0.016666666666666666,
    "knee_flux_pu": 0.5,
    "cases": [
      {
        "closing_angle_deg": 90,
        "minimum_flux_pu": -0.9999999999999999,
        "maximum_flux_pu": 1.0,
        "peak_flux_pu": 1.0,
        "knee_exceeded": true,
        "above_knee_seconds": 0.011111111111111113,
        "peak_magnetizing_current_a": 20.0,
        "first_cycle_rms_magnetizing_current_a": 12.759379747519553,
        "first_cycle_mean_current_a": 2.393712567841811e-15,
        "first_cycle_harmonic_rms_a": {
          "1": 12.600673966070907,
          "2": 1.0874865364331296e-15,
          "3": 1.9492425124743626,
          "5": 0.38984865155141907,
          "7": 0.1392318316134053
        },
        "rms_sample_count": 4096
      }
    ]
  }
}