  "passed": true,
  "result": {
    "study": "IEC maximum three-phase bolted fault",
    "fault_location": "FAULT",
    "initial_symmetrical_rms_ka": 16.97818263508776,
    "contributions": [
      {
        "source": "U-A",
        "feeder": "F-A",
        "real_ka": 8.314548276271747,
        "imag_ka": -5.8493497326708095,
        "magnitude_ka": 10.165953242738702,
        "angle_deg": -35.126686135639204
      },
      {
        "source": "U-B",
        "feeder": "F-B",
        "real_ka": 2.898500386071339,
        "imag_ka": -6.899227650171618,
        "magnitude_ka": 7.483357980007924,
        "angle_deg": -67.21177212422494
      }
    ],
    "excluded_feeders": [],
    "scope": "Parallel independent same-voltage radial sources"
  },
  "one_feeder_open_ka": 10.165953242738702,
  "all_open_rejected": true,
  "reference_tolerance_ka": 0.001
}