  "passed": true,
  "handoff": {
    "scope": "Input handoff and provenance only",
    "source_study": "IEC maximum three-phase bolted fault",
    "source_network_sha256": "d6f6fc1ac3ddfd79ba8c6ac778061e7875d65599568833f0c713451793938118",
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "destination_settings_sha256": "44136fa355b3678a1146ad16f7e8649e94fb4fc21fe77e8310c060f61caaff8a",
    "fault_bus": "FEEDER-END",
    "fault_type": "3ph",
    "transferred": {
      "nominal_voltage_kv": 0.4,
      "bolted_fault_current_ka_rms": 8.962416883591409
    },
    "destination_settings": {},
    "missing_inputs": [
      "method",
      "electrode_configuration",
      "enclosure_mm",
      "conductor_gap_mm",
      "working_distance_mm",
      "clearing_time_basis"
    ],
    "status": "missing_inputs",
    "bolted_fault_duty_reference": {
      "study": "Synthetic constant-RMS I-squared-t screen",
      "fault_bus": "FEEDER-END",
      "equipment_id": "DUTY-LOW",
      "initial_rms_ka": 8.962416883591409,
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "9ef15e3a8d2026e1a5275642814438d4b610c665af102fd496273f8345bf0a34",
      "clearing_seconds": 0.07967639790006337,
      "screening_ka2_seconds": 6.3999999999999995,
      "withstand_ka2_seconds": 10.0,
      "status": "below_rating",
      "thermal_margin_ka2_seconds": 3.6000000000000005,
      "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
      "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
    },
    "duty_reference_scope": "Bolted-fault screen only. Arcing-current clearing time requires a separate assessment.",
    "study_input_sha256": "96ee65ae8961626728720323604b0e71b62d4aaf8acd7201c99606666a95fc94",
    "handoff_input_sha256": "e4b586ce53b4f6121adcfcbf826d24287e7a68364f93c90e22a9407b481ee9a2"
  },
  "changed_rating": {
    "study": "Synthetic constant-RMS I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "48eedd78fa65ef946fe169b3483dfd59ffba9ddecaca278c310692ac79e039ef",
    "clearing_seconds": 0.07967639790006337,
    "screening_ka2_seconds": 6.3999999999999995,
    "withstand_ka2_seconds": 40.0,
    "status": "below_rating",
    "thermal_margin_ka2_seconds": 33.6,
    "constant_initial_rms_duration_at_rating_s": 0.4979774868753961,
    "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
  },
  "changed_duty_handoff_sha256": "85aa086fb15ab0e10dec68439e8e5d1d97edaedaf8805a22c4d5d0502c72a869",
  "baseline_duty_handoff_sha256": "e4b586ce53b4f6121adcfcbf826d24287e7a68364f93c90e22a9407b481ee9a2",
  "different_bus_excluded": true,
  "arcing_handoff": {
    "scope": "Input handoff and provenance only",
    "source_study": "IEC maximum three-phase bolted fault",
    "source_network_sha256": "d6f6fc1ac3ddfd79ba8c6ac778061e7875d65599568833f0c713451793938118",
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "destination_settings_sha256": "e6fe474e682be2f8b1be68def2b3803d7b8f1c73c90f8ec9e4c6250022cc99e9",
    "fault_bus": "FEEDER-END",
    "fault_type": "3ph",
    "transferred": {
      "nominal_voltage_kv": 0.4,
      "bolted_fault_current_ka_rms": 8.962416883591409
    },
    "destination_settings": {
      "arcing_clearance": {
        "device_id": "SYNTHETIC",
        "curve_source": "Synthetic regression fixture",
        "trip_band": [
          [
            2,
            0.2,
            0.4
          ],
          [
            8,
            0.05,
            0.1
          ]
        ],
        "cases_ka": {
          "nominal": 8,
          "reduced": 4
        }
      }
    },
    "missing_inputs": [
      "method",
      "electrode_configuration",
      "enclosure_mm",
      "conductor_gap_mm",
      "working_distance_mm",
      "clearing_time_basis"
    ],
    "status": "missing_inputs",
    "bolted_fault_duty_reference": {
      "study": "Synthetic constant-RMS I-squared-t screen",
      "fault_bus": "FEEDER-END",
      "equipment_id": "DUTY-LOW",
      "initial_rms_ka": 8.962416883591409,
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "9ef15e3a8d2026e1a5275642814438d4b610c665af102fd496273f8345bf0a34",
      "clearing_seconds": 0.07967639790006337,
      "screening_ka2_seconds": 6.3999999999999995,
      "withstand_ka2_seconds": 10.0,
      "status": "below_rating",
      "thermal_margin_ka2_seconds": 3.6000000000000005,
      "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
      "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
    },
    "duty_reference_scope": "Bolted-fault screen only. Arcing-current clearing time requires a separate assessment.",
    "arcing_clearance": {
      "scope": "Supplied arcing currents and total clearing-time band",
      "device_id": "SYNTHETIC",
      "curve_source": "Synthetic regression fixture",
      "input_sha256": "4451df64df57556b83000facac0c9102be7c2826cab8e877be17354463a29164",
      "cases": {
        "nominal": {
          "arcing_current_ka": 8,
          "earliest_seconds": 0.05,
          "latest_seconds": 0.1,
          "status": "covered"
        },
        "reduced": {
          "arcing_current_ka": 4,
          "earliest_seconds": 0.1,
          "latest_seconds": 0.2,
          "status": "covered"
        }
      },
      "longest_latest_seconds": 0.2,
      "longest_clearing_case_ids": [
        "reduced"
      ],
      "status": "covered"
    },
    "study_input_sha256": "aa05b4e5c7badb56acc55b88e4ceaf8a2c876ef1b60509e614384bc1c2cf04ba",
    "handoff_input_sha256": "13c1ce42f86bf6facc7aaf1d79c0d4133c948f602157babc8ad6df81413d0084"
  },
  "changed_curve_report": {
    "scope": "Supplied arcing currents and total clearing-time band",
    "device_id": "SYNTHETIC",
    "curve_source": "Synthetic regression fixture",
    "input_sha256": "9dbd4a80b995ab5f6cf7262e747987a3b4d4509458c6dac85ccefc03c1838c4e",
    "cases": {
      "nominal": {
        "arcing_current_ka": 8,
        "earliest_seconds": 0.05,
        "latest_seconds": 0.15,
        "status": "covered"
      },
      "reduced": {
        "arcing_current_ka": 4,
        "earliest_seconds": 0.1,
        "latest_seconds": 0.2449489742783178,
        "status": "covered"
      }
    },
    "longest_latest_seconds": 0.2449489742783178,
    "longest_clearing_case_ids": [
      "reduced"
    ],
    "status": "covered"
  },
  "profile_duty": {
    "study": "Supplied RMS profile I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "5a8d2e35c7f807564360fc0524c2a511ed6b22fe159a177bbae9b0b699d879aa",
    "clearing_seconds": 0.3,
    "screening_ka2_seconds": 8.032491639528436,
    "withstand_ka2_seconds": 10.0,
    "status": "below_rating",
    "thermal_margin_ka2_seconds": 1.9675083604715642,
    "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
    "scope": "Piecewise-linear RMS current through the supplied clearing point. Clearing is not predicted.",
    "profile_summary": {
      "sample_count": 3,
      "thermal_limit_reached_at_s": null,
      "cumulative_ka2_seconds_at_samples": [
        0.0,
        7.028430184587381,
        8.032491639528436
      ],
      "final_sample_rms_ka": 0,
      "maximum_sample_rms_ka": 8.962416883591409,
      "equivalent_constant_rms_ka": 5.174453800331148
    }
  },
  "time_duty_csv_samples_verified": 3,
  "profile_thermal_crossing": {
    "study": "Supplied RMS profile I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "565afde91b3631fbcb85bcfe97c474433002894dab85bc1b3d5daa189eaadc1c",
    "clearing_seconds": 0.3,
    "screening_ka2_seconds": 8.032491639528436,
    "withstand_ka2_seconds": 4.643784229102376,
    "status": "exceeds_rating",
    "thermal_margin_ka2_seconds": -3.3887074104260595,
    "constant_initial_rms_duration_at_rating_s": 0.0578125,
    "scope": "Piecewise-linear RMS current through the supplied clearing point. Clearing is not predicted.",
    "profile_summary": {
      "sample_count": 3,
      "thermal_limit_reached_at_s": 0.07500000000000001,
      "cumulative_ka2_seconds_at_samples": [
        0.0,
        7.028430184587381,
        8.032491639528436
      ],
      "final_sample_rms_ka": 0,
      "maximum_sample_rms_ka": 8.962416883591409,
      "equivalent_constant_rms_ka": 5.174453800331148
    }
  },
  "named_radial_duty": {
    "study": "Synthetic constant-RMS I-squared-t screen",
    "fault_bus": "FAULT",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 5.6415374480783145,
    "source_fault_sha256": "02d682060783a0a4339f4fe20299feca6d21670fab73505ab4b20c8e5932ec3a",
    "duty_settings_sha256": "e6fcaa9093403265d68fd1b12237d2c6d5c74c56bf5180e905785367b52f562f",
    "clearing_seconds": 0.1,
    "screening_ka2_seconds": 3.182694477806998,
    "withstand_ka2_seconds": 10.0,
    "status": "below_rating",
    "thermal_margin_ka2_seconds": 6.817305522193002,
    "constant_initial_rms_duration_at_rating_s": 0.3141991815340816,
    "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
  },
  "direct_named_fault": {
    "study": "IEC maximum bolted fault",
    "fault_type": "3ph",
    "fault_location": "FAULT",
    "initial_symmetrical_rms_ka": 5.6415374480783145,
    "equipment_path": [
      "U1",
      "F1"
    ],
    "positive_sequence_r_x_ohm": [
      0.3512456529119184,
      1.9124565291191837
    ],
    "negative_sequence_r_x_ohm": [
      0.3512456529119184,
      1.9124565291191837
    ],
    "zero_sequence_r_x_ohm": null,
    "scope": "Single same-voltage radial feeder with Z2 equal to Z1",
    "phase_rms_ka": {
      "A": 5.6415374480783145,
      "B": 5.6415374480783145,
      "C": 5.6415374480783145
    }
  },
  "named_duty_override": {
    "study": "Supplied RMS profile I-squared-t screen",
    "fault_bus": "FAULT",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 5.6415374480783145,
    "source_fault_sha256": "02d682060783a0a4339f4fe20299feca6d21670fab73505ab4b20c8e5932ec3a",
    "duty_settings_sha256": "bc3944e7be4d6804ae7382fc155db5e0e31170b7c7f2ad3e530ae0a5afb1aacf",
    "clearing_seconds": 0.12,
    "screening_ka2_seconds": 1.273077791122799,
    "withstand_ka2_seconds": 10.0,
    "status": "below_rating",
    "thermal_margin_ka2_seconds": 8.726922208877202,
    "constant_initial_rms_duration_at_rating_s": 0.3141991815340816,
    "scope": "Piecewise-linear RMS current through the supplied clearing point. Clearing is not predicted.",
    "profile_summary": {
      "sample_count": 2,
      "thermal_limit_reached_at_s": null,
      "cumulative_ka2_seconds_at_samples": [
        0.0,
        1.273077791122799
      ],
      "final_sample_rms_ka": 0,
      "maximum_sample_rms_ka": 5.6415374480783145,
      "equivalent_constant_rms_ka": 3.257143164291369
    }
  },
  "batch_time_duty": {
    "scope": "Thermal duty comparison for saved radial fault cases",
    "cases": {
      "high-voltage": {
        "study": "Synthetic constant-RMS I-squared-t screen",
        "fault_bus": "FAULT",
        "equipment_id": "SECONDARY-DEVICE",
        "initial_rms_ka": 5.816526864040774,
        "source_fault_sha256": "f7522575778516dc219a21d6ebe16cb4190728c37a97d4d96ef453477a4d2675",
        "duty_settings_sha256": "030f0adaf2cf552ba5e21d974b36888066e1905cfcd624b0d7ac1ff51a561888",
        "clearing_seconds": 0.1,
        "screening_ka2_seconds": 3.3831984760108003,
        "withstand_ka2_seconds": 0.0010000000000000002,
        "status": "exceeds_rating",
        "thermal_margin_ka2_seconds": -3.3821984760108004,
        "constant_initial_rms_duration_at_rating_s": 2.9557828400866423e-05,
        "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
      },
      "low-voltage": {
        "study": "Supplied RMS profile I-squared-t screen",
        "fault_bus": "FAULT",
        "equipment_id": "DUTY-LOW",
        "initial_rms_ka": 5.6415374480783145,
        "source_fault_sha256": "02d682060783a0a4339f4fe20299feca6d21670fab73505ab4b20c8e5932ec3a",
        "duty_settings_sha256": "bc3944e7be4d6804ae7382fc155db5e0e31170b7c7f2ad3e530ae0a5afb1aacf",
        "clearing_seconds": 0.12,
        "screening_ka2_seconds": 1.273077791122799,
        "withstand_ka2_seconds": 10.0,
        "status": "below_rating",
        "thermal_margin_ka2_seconds": 8.726922208877202,
        "constant_initial_rms_duration_at_rating_s": 0.3141991815340816,
        "scope": "Piecewise-linear RMS current through the supplied clearing point. Clearing is not predicted.",
        "profile_summary": {
          "sample_count": 2,
          "thermal_limit_reached_at_s": null,
          "cumulative_ka2_seconds_at_samples": [
            0.0,
            1.273077791122799
          ],
          "final_sample_rms_ka": 0,
          "maximum_sample_rms_ka": 5.6415374480783145,
          "equivalent_constant_rms_ka": 3.257143164291369
        }
      }
    },
    "thermal_utilization_by_case": {
      "high-voltage": 3383.1984760107994,
      "low-voltage": 0.12730777911227992
    },
    "equipment_summary": {
      "SECONDARY-DEVICE": {
        "unresolved_cases": [],
        "maximum_thermal_utilization": 3383.1984760107994,
        "governing_cases": [
          "high-voltage"
        ]
      },
      "DUTY-LOW": {
        "unresolved_cases": [],
        "maximum_thermal_utilization": 0.12730777911227992,
        "governing_cases": [
          "low-voltage"
        ]
      }
    },
    "unresolved_cases": [],
    "maximum_thermal_utilization": 3383.1984760107994,
    "governing_cases": [
      "high-voltage"
    ]
  },
  "batch_duty_csv_rows_verified": 2,
  "batch_duty_csv_margins_verified": true,
  "arc_sheet_duty_rows_verified": 2,
  "arc_sheet_radial_band": {
    "study": "Supplied RMS profile clearing-band I-squared-t screen",
    "fault_bus": "FAULT",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 5.6415374480783145,
    "source_fault_sha256": "02d682060783a0a4339f4fe20299feca6d21670fab73505ab4b20c8e5932ec3a",
    "duty_settings_sha256": "8c68598864c583057a7f395587b0154313a2ff92dc8c889c6c9e9a05a122045c",
    "clearing_seconds": 0.1,
    "screening_ka2_seconds": 7.903691286554046,
    "withstand_ka2_seconds": 10.0,
    "status": "below_rating",
    "thermal_margin_ka2_seconds": 2.0963087134459544,
    "constant_initial_rms_duration_at_rating_s": 0.3141991815340816,
    "scope": "Integrates the supplied RMS profile at clearing bounds evaluated at initial RMS current.",
    "clearing_bounds_seconds": [
      0.05,
      0.1
    ],
    "duty_bounds_ka2_seconds": [
      2.7931459349504117,
      7.903691286554046
    ],
    "thermal_crossing_vs_clearing_band": "not_reached_by_latest",
    "interrupting_band_rms_screen": {
      "rating_ka": 8.462306172117472,
      "maximum_clearing_window_rms_ka": 11.283074896156629,
      "governing_time_s": 0.08,
      "status": "exceeds_rating",
      "scope": "Supplied symmetrical RMS over the modeled clearing window"
    },
    "asymmetrical_band_rms_screen": {
      "rating_ka_rms": 11.283074896156629,
      "maximum_clearing_window_rms_ka": 11.564321356715249,
      "governing_time_s": 0.08,
      "governing_symmetrical_rms_ka": 11.283074896156629,
      "governing_dc_component_ka": 2.534906177573543,
      "status": "exceeds_rating",
      "scope": "Quadrature of supplied symmetrical RMS and instantaneous decaying DC offset"
    }
  },
  "batch_band_csv": {
    "high-voltage": {
      "case_id": "high-voltage",
      "equipment_id": "SECONDARY-DEVICE",
      "source_fault_sha256": "f7522575778516dc219a21d6ebe16cb4190728c37a97d4d96ef453477a4d2675",
      "duty_settings_sha256": "6af633acf348dec600d9fb056daa2c13f0a1145b82cbc0def883e154b0836d32",
      "status": "outside_curve",
      "clearing_seconds": "",
      "screening_ka2_seconds": "",
      "withstand_ka2_seconds": "0.0010000000000000002",
      "thermal_margin_ka2_seconds": "",
      "thermal_utilization": "",
      "governing": "False",
      "earliest_clearing_seconds": "",
      "earliest_duty_ka2_seconds": "",
      "symmetrical_interrupting_maximum_rms_ka": "",
      "symmetrical_interrupting_rating_rms_ka": "",
      "symmetrical_interrupting_governing_time_s": "",
      "symmetrical_interrupting_status": "",
      "asymmetrical_interrupting_maximum_rms_ka": "",
      "asymmetrical_interrupting_rating_rms_ka": "",
      "asymmetrical_interrupting_governing_time_s": "",
      "asymmetrical_interrupting_status": ""
    },
    "low-voltage": {
      "case_id": "low-voltage",
      "equipment_id": "DUTY-LOW",
      "source_fault_sha256": "02d682060783a0a4339f4fe20299feca6d21670fab73505ab4b20c8e5932ec3a",
      "duty_settings_sha256": "8c68598864c583057a7f395587b0154313a2ff92dc8c889c6c9e9a05a122045c",
      "status": "below_rating",
      "clearing_seconds": "0.1",
      "screening_ka2_seconds": "7.903691286554046",
      "withstand_ka2_seconds": "10.0",
      "thermal_margin_ka2_seconds": "2.0963087134459544",
      "thermal_utilization": "0.7903691286554045",
      "governing": "False",
      "earliest_clearing_seconds": "0.05",
      "earliest_duty_ka2_seconds": "2.7931459349504117",
      "symmetrical_interrupting_maximum_rms_ka": "11.283074896156629",
      "symmetrical_interrupting_rating_rms_ka": "8.462306172117472",
      "symmetrical_interrupting_governing_time_s": "0.08",
      "symmetrical_interrupting_status": "exceeds_rating",
      "asymmetrical_interrupting_maximum_rms_ka": "11.564321356715249",
      "asymmetrical_interrupting_rating_rms_ka": "11.283074896156629",
      "asymmetrical_interrupting_governing_time_s": "0.08",
      "asymmetrical_interrupting_status": "exceeds_rating"
    }
  },
  "interpolated_radial_duty": {
    "study": "Synthetic constant-RMS I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "158c3e39f4ca50b0a5335f25494dce0a0306b48a082508106a34bcadba71dd27",
    "clearing_seconds": 0.6000000000000001,
    "screening_ka2_seconds": 48.19494983717062,
    "withstand_ka2_seconds": 10.0,
    "status": "exceeds_rating",
    "thermal_margin_ka2_seconds": -38.19494983717062,
    "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
    "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope.",
    "clearing_bounds_seconds": [
      0.2,
      0.6000000000000001
    ],
    "duty_bounds_ka2_seconds": [
      16.06498327905687,
      48.19494983717062
    ]
  },
  "profile_at_clearing_bounds": {
    "study": "Supplied RMS profile clearing-band I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "77ccb7d7293cf9ded1140fc595fbc3385ac1647680d5681fa5f4424e7fe50c74",
    "clearing_seconds": 0.6000000000000001,
    "screening_ka2_seconds": 21.085290553762142,
    "withstand_ka2_seconds": 10.0,
    "status": "exceeds_rating",
    "thermal_margin_ka2_seconds": -11.085290553762142,
    "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
    "scope": "Integrates the supplied RMS profile at clearing bounds evaluated at initial RMS current.",
    "clearing_bounds_seconds": [
      0.2,
      0.6000000000000001
    ],
    "duty_bounds_ka2_seconds": [
      12.383424610939668,
      21.085290553762142
    ],
    "thermal_limit_reached_at_s": 0.1513077129661512,
    "thermal_crossing_vs_clearing_band": "reached_by_earliest"
  },
  "profile_band_csv_rows": [
    {
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "b4dc5ac569e203f98594b1d81f6b7db668b76587e7eff8b06915187ec1cf82d1",
      "time_s": "0",
      "current_ka_rms": "8.962416883591409",
      "cumulative_ka2_seconds": "0.0",
      "withstand_ka2_seconds": "10.0",
      "thermal_limit_reached_at_s": "0.15130771296615114",
      "thermal_crossing_vs_clearing_band": "reached_by_earliest"
    },
    {
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "b4dc5ac569e203f98594b1d81f6b7db668b76587e7eff8b06915187ec1cf82d1",
      "time_s": "0.2",
      "current_ka_rms": "6.721812662693557",
      "cumulative_ka2_seconds": "12.383424610939668",
      "withstand_ka2_seconds": "10.0",
      "thermal_limit_reached_at_s": "0.15130771296615114",
      "thermal_crossing_vs_clearing_band": "reached_by_earliest"
    },
    {
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "b4dc5ac569e203f98594b1d81f6b7db668b76587e7eff8b06915187ec1cf82d1",
      "time_s": "0.4",
      "current_ka_rms": "4.4812084417957045",
      "cumulative_ka2_seconds": "18.742480492233014",
      "withstand_ka2_seconds": "10.0",
      "thermal_limit_reached_at_s": "0.15130771296615114",
      "thermal_crossing_vs_clearing_band": "reached_by_earliest"
    },
    {
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "b4dc5ac569e203f98594b1d81f6b7db668b76587e7eff8b06915187ec1cf82d1",
      "time_s": "0.6000000000000001",
      "current_ka_rms": "2.240604220897852",
      "cumulative_ka2_seconds": "21.08529055376214",
      "withstand_ka2_seconds": "10.0",
      "thermal_limit_reached_at_s": "0.15130771296615114",
      "thermal_crossing_vs_clearing_band": "reached_by_earliest"
    }
  ],
  "interrupting_window_screen": {
    "rating_ka": 17.028592078823678,
    "maximum_clearing_window_rms_ka": 17.924833767182818,
    "governing_time_s": 0.4,
    "status": "exceeds_rating",
    "scope": "Supplied symmetrical RMS over the modeled clearing window"
  },
  "asymmetrical_interrupting_window_screen": {
    "rating_ka_rms": 17.924833767182818,
    "maximum_clearing_window_rms_ka": 18.371635379289376,
    "governing_time_s": 0.4,
    "governing_symmetrical_rms_ka": 17.924833767182818,
    "governing_dc_component_ka": 4.027073494290825,
    "status": "exceeds_rating",
    "scope": "Quadrature of supplied symmetrical RMS and instantaneous decaying DC offset"
  },
  "dc_averaged_band_screen": {
    "rating_ka_rms": 17.924833767182818,
    "maximum_clearing_window_rms_ka": 18.472678825404994,
    "governing_time_s": 0.4,
    "governing_symmetrical_rms_ka": 17.924833767182818,
    "governing_dc_component_ka": 4.465444816076969,
    "status": "exceeds_rating",
    "scope": "Quadrature of supplied symmetrical RMS and DC RMS over a trailing window",
    "dc_rms_window_s": 0.1
  },
  "inverted_radial_band_rejected": true,
  "unresolved_batch_time_duty": {
    "scope": "Thermal duty comparison for saved radial fault cases",
    "cases": {
      "high-voltage": {
        "study": "Synthetic constant-RMS I-squared-t screen",
        "fault_bus": "FAULT",
        "equipment_id": "SECONDARY-DEVICE",
        "initial_rms_ka": 5.816526864040774,
        "source_fault_sha256": "f7522575778516dc219a21d6ebe16cb4190728c37a97d4d96ef453477a4d2675",
        "duty_settings_sha256": "6af633acf348dec600d9fb056daa2c13f0a1145b82cbc0def883e154b0836d32",
        "clearing_seconds": null,
        "screening_ka2_seconds": null,
        "withstand_ka2_seconds": 0.0010000000000000002,
        "status": "outside_curve",
        "thermal_margin_ka2_seconds": null,
        "constant_initial_rms_duration_at_rating_s": 2.9557828400866423e-05,
        "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
      },
      "low-voltage": {
        "study": "Supplied RMS profile I-squared-t screen",
        "fault_bus": "FAULT",
        "equipment_id": "DUTY-LOW",
        "initial_rms_ka": 5.6415374480783145,
        "source_fault_sha256": "02d682060783a0a4339f4fe20299feca6d21670fab73505ab4b20c8e5932ec3a",
        "duty_settings_sha256": "bc3944e7be4d6804ae7382fc155db5e0e31170b7c7f2ad3e530ae0a5afb1aacf",
        "clearing_seconds": 0.12,
        "screening_ka2_seconds": 1.273077791122799,
        "withstand_ka2_seconds": 10.0,
        "status": "below_rating",
        "thermal_margin_ka2_seconds": 8.726922208877202,
        "constant_initial_rms_duration_at_rating_s": 0.3141991815340816,
        "scope": "Piecewise-linear RMS current through the supplied clearing point. Clearing is not predicted.",
        "profile_summary": {
          "sample_count": 2,
          "thermal_limit_reached_at_s": null,
          "cumulative_ka2_seconds_at_samples": [
            0.0,
            1.273077791122799
          ],
          "final_sample_rms_ka": 0,
          "maximum_sample_rms_ka": 5.6415374480783145,
          "equivalent_constant_rms_ka": 3.257143164291369
        }
      }
    },
    "thermal_utilization_by_case": {
      "low-voltage": 0.12730777911227992
    },
    "equipment_summary": {
      "SECONDARY-DEVICE": {
        "unresolved_cases": [
          "high-voltage"
        ],
        "maximum_thermal_utilization": null,
        "governing_cases": []
      },
      "DUTY-LOW": {
        "unresolved_cases": [],
        "maximum_thermal_utilization": 0.12730777911227992,
        "governing_cases": [
          "low-voltage"
        ]
      }
    },
    "unresolved_cases": [
      "high-voltage"
    ],
    "maximum_thermal_utilization": null,
    "governing_cases": []
  },
  "orphaned_duty_override_rejected": true,
  "nonmonotonic_profile": {
    "study": "Supplied RMS profile I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "73e0eca4d3a86b5251d948266f6f303bfe97ed1df250c604c7f5b84b97235521",
    "clearing_seconds": 0.2,
    "screening_ka2_seconds": 32.79934086140778,
    "withstand_ka2_seconds": 10.0,
    "status": "exceeds_rating",
    "thermal_margin_ka2_seconds": -22.799340861407778,
    "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
    "scope": "Piecewise-linear RMS current through the supplied clearing point. Clearing is not predicted.",
    "profile_summary": {
      "sample_count": 3,
      "thermal_limit_reached_at_s": 0.06791964164684974,
      "cumulative_ka2_seconds_at_samples": [
        0.0,
        18.742480492233017,
        32.79934086140778
      ],
      "final_sample_rms_ka": 4.4812084417957045,
      "maximum_sample_rms_ka": 17.924833767182818,
      "equivalent_constant_rms_ka": 12.806119799027295
    }
  },
  "interrupting_checks": {
    "exceeds_rating": {
      "rating_ka": 2.2406042208978523,
      "final_sample_rms_ka": 4.4812084417957045,
      "status": "exceeds_rating",
      "scope": "Supplied symmetrical RMS comparison only. Review asymmetry and device applicability."
    },
    "at_rating": {
      "rating_ka": 4.4812084417957045,
      "final_sample_rms_ka": 4.4812084417957045,
      "status": "at_rating",
      "scope": "Supplied symmetrical RMS comparison only. Review asymmetry and device applicability."
    },
    "below_rating": {
      "rating_ka": 8.962416883591409,
      "final_sample_rms_ka": 4.4812084417957045,
      "status": "below_rating",
      "scope": "Supplied symmetrical RMS comparison only. Review asymmetry and device applicability."
    }
  },
  "asymmetrical_duty": {
    "study": "Supplied RMS profile I-squared-t screen",
    "fault_bus": "FEEDER-END",
    "equipment_id": "DUTY-LOW",
    "initial_rms_ka": 8.962416883591409,
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "duty_settings_sha256": "35c41c063bf4deb45984da9b1e0aea9f29d0691cffc15d6c9dd0b30c4c0fdd25",
    "clearing_seconds": 0.2,
    "screening_ka2_seconds": 32.79934086140778,
    "withstand_ka2_seconds": 10.0,
    "status": "exceeds_rating",
    "thermal_margin_ka2_seconds": -22.799340861407778,
    "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
    "scope": "Piecewise-linear RMS current through the supplied clearing point. Clearing is not predicted.",
    "profile_summary": {
      "sample_count": 3,
      "thermal_limit_reached_at_s": 0.06791964164684974,
      "cumulative_ka2_seconds_at_samples": [
        0.0,
        18.742480492233017,
        32.79934086140778
      ],
      "final_sample_rms_ka": 4.4812084417957045,
      "maximum_sample_rms_ka": 17.924833767182818,
      "equivalent_constant_rms_ka": 12.806119799027295
    },
    "interrupting_rms_screen": {
      "rating_ka": 8.962416883591409,
      "final_sample_rms_ka": 4.4812084417957045,
      "status": "below_rating",
      "scope": "Supplied symmetrical RMS comparison only. Review asymmetry and device applicability."
    },
    "asymmetrical_rms_screen": {
      "rating_ka_rms": 5.377450130154846,
      "dc_offset_ka_at_final_sample": -3.3609063313467784,
      "dc_offset_basis": "supplied_final_sample",
      "dc_component_rms_ka": 3.3609063313467784,
      "dc_rms_window_s": null,
      "combined_rms_ka": 5.601510552244631,
      "status": "exceeds_rating",
      "scope": "Quadrature screen with final symmetrical RMS. Cross terms between AC and DC are excluded."
    }
  },
  "decayed_dc_screen": {
    "rating_ka_rms": 5.377450130154846,
    "dc_offset_ka_at_final_sample": -3.3609063313467784,
    "dc_offset_basis": "single_exponential",
    "dc_component_rms_ka": 3.3609063313467784,
    "dc_rms_window_s": null,
    "combined_rms_ka": 5.601510552244631,
    "status": "exceeds_rating",
    "scope": "Quadrature screen with final symmetrical RMS. Cross terms between AC and DC are excluded."
  },
  "windowed_dc_screen": {
    "rating_ka_rms": 5.377450130154846,
    "dc_offset_ka_at_final_sample": -3.3609063313467784,
    "dc_offset_basis": "single_exponential",
    "dc_component_rms_ka": 4.944123469354985,
    "dc_rms_window_s": 0.2,
    "combined_rms_ka": 6.672749506691216,
    "status": "exceeds_rating",
    "scope": "Quadrature screen with final symmetrical RMS. Cross terms between AC and DC are excluded."
  },
  "window_before_fault_rejected": true,
  "ambiguous_dc_basis_rejected": true,
  "missing_profile_rejected": true,
  "inconsistent_initial_profile_rejected": true,
  "pinned_incident_energy_handoff": {
    "scope": "Input handoff and provenance only",
    "source_study": "IEC maximum three-phase bolted fault",
    "source_network_sha256": "d6f6fc1ac3ddfd79ba8c6ac778061e7875d65599568833f0c713451793938118",
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "destination_settings_sha256": "98a8f8fcb3bb9ab0eede49922b6d940537b4e4e8b0cddf744188b1bd1f61c6a8",
    "fault_bus": "FEEDER-END",
    "fault_type": "3ph",
    "transferred": {
      "nominal_voltage_kv": 0.4,
      "bolted_fault_current_ka_rms": 8.962416883591409
    },
    "destination_settings": {
      "method": "Synthetic",
      "electrode_configuration": "VCB",
      "enclosure_mm": [
        500,
        500,
        300
      ],
      "conductor_gap_mm": 30,
      "working_distance_mm": 450,
      "clearing_time_basis": "Total clearing",
      "arcing_clearance": {
        "device_id": "SYNTHETIC",
        "curve_source": "Synthetic regression fixture",
        "trip_band": [
          [
            2,
            0.2,
            0.4
          ],
          [
            8,
            0.05,
            0.1
          ]
        ],
        "cases_ka": {
          "nominal": 8,
          "reduced": 4
        }
      },
      "incident_energy_results": {
        "study_input_sha256": "53026846e2a23f03dc6686efad2245a3c9973ac040859a0e791a3f4da1533006",
        "source": "Synthetic fixture",
        "cases_cal_per_cm2": {
          "nominal": 6,
          "reduced": 4
        },
        "handoff_input_sha256": "192d7aa5fc5b67fdc9f2ad2a45782adb4d108dffc342b80b17a553e30e570aaf"
      }
    },
    "missing_inputs": [],
    "status": "inputs_present",
    "bolted_fault_duty_reference": {
      "study": "Synthetic constant-RMS I-squared-t screen",
      "fault_bus": "FEEDER-END",
      "equipment_id": "DUTY-LOW",
      "initial_rms_ka": 8.962416883591409,
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "9ef15e3a8d2026e1a5275642814438d4b610c665af102fd496273f8345bf0a34",
      "clearing_seconds": 0.07967639790006337,
      "screening_ka2_seconds": 6.3999999999999995,
      "withstand_ka2_seconds": 10.0,
      "status": "below_rating",
      "thermal_margin_ka2_seconds": 3.6000000000000005,
      "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
      "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
    },
    "duty_reference_scope": "Bolted-fault screen only. Arcing-current clearing time requires a separate assessment.",
    "arcing_clearance": {
      "scope": "Supplied arcing currents and total clearing-time band",
      "device_id": "SYNTHETIC",
      "curve_source": "Synthetic regression fixture",
      "input_sha256": "4451df64df57556b83000facac0c9102be7c2826cab8e877be17354463a29164",
      "cases": {
        "nominal": {
          "arcing_current_ka": 8,
          "earliest_seconds": 0.05,
          "latest_seconds": 0.1,
          "status": "covered"
        },
        "reduced": {
          "arcing_current_ka": 4,
          "earliest_seconds": 0.1,
          "latest_seconds": 0.2,
          "status": "covered"
        }
      },
      "longest_latest_seconds": 0.2,
      "longest_clearing_case_ids": [
        "reduced"
      ],
      "status": "covered"
    },
    "study_input_sha256": "53026846e2a23f03dc6686efad2245a3c9973ac040859a0e791a3f4da1533006",
    "handoff_input_sha256": "192d7aa5fc5b67fdc9f2ad2a45782adb4d108dffc342b80b17a553e30e570aaf",
    "incident_energy_review": {
      "scope": "Comparison of supplied incident-energy results",
      "source": "Synthetic fixture",
      "study_input_sha256": "53026846e2a23f03dc6686efad2245a3c9973ac040859a0e791a3f4da1533006",
      "report_sha256": "a957fe11aacbec6cce5d6287890b141f0dc0e6eca1ddc217cfaeed37e11259ff",
      "handoff_input_sha256": "192d7aa5fc5b67fdc9f2ad2a45782adb4d108dffc342b80b17a553e30e570aaf",
      "clearing_input_sha256": "4451df64df57556b83000facac0c9102be7c2826cab8e877be17354463a29164",
      "clearing_device_id": "SYNTHETIC",
      "clearing_curve_source": "Synthetic regression fixture",
      "cases": {
        "nominal": {
          "arcing_current_ka": 8,
          "earliest_seconds": 0.05,
          "latest_seconds": 0.1,
          "status": "covered",
          "incident_energy_cal_per_cm2": 6
        },
        "reduced": {
          "arcing_current_ka": 4,
          "earliest_seconds": 0.1,
          "latest_seconds": 0.2,
          "status": "covered",
          "incident_energy_cal_per_cm2": 4
        }
      },
      "maximum_cal_per_cm2": 6,
      "maximum_case_ids": [
        "nominal"
      ]
    }
  },
  "stale_equipment_duty_rejected": true,
  "existing_output_preserved_after_rejection": true,
  "incident_energy_review": {
    "scope": "Input handoff and provenance only",
    "source_study": "IEC maximum three-phase bolted fault",
    "source_network_sha256": "d6f6fc1ac3ddfd79ba8c6ac778061e7875d65599568833f0c713451793938118",
    "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
    "destination_settings_sha256": "19e4c859bdd8f2f042b51bb561f14857677d998cdda523d526e91ad20cdc76cf",
    "fault_bus": "FEEDER-END",
    "fault_type": "3ph",
    "transferred": {
      "nominal_voltage_kv": 0.4,
      "bolted_fault_current_ka_rms": 8.962416883591409
    },
    "destination_settings": {
      "method": "Synthetic",
      "electrode_configuration": "VCB",
      "enclosure_mm": [
        500,
        500,
        300
      ],
      "conductor_gap_mm": 30,
      "working_distance_mm": 450,
      "clearing_time_basis": "Total clearing",
      "arcing_clearance": {
        "device_id": "SYNTHETIC",
        "curve_source": "Synthetic regression fixture",
        "trip_band": [
          [
            2,
            0.2,
            0.4
          ],
          [
            8,
            0.05,
            0.1
          ]
        ],
        "cases_ka": {
          "nominal": 8,
          "reduced": 4
        }
      },
      "incident_energy_results": {
        "study_input_sha256": "53026846e2a23f03dc6686efad2245a3c9973ac040859a0e791a3f4da1533006",
        "source": "Synthetic fixture",
        "cases_cal_per_cm2": {
          "nominal": 6,
          "reduced": 4
        }
      }
    },
    "missing_inputs": [],
    "status": "inputs_present",
    "bolted_fault_duty_reference": {
      "study": "Synthetic constant-RMS I-squared-t screen",
      "fault_bus": "FEEDER-END",
      "equipment_id": "DUTY-LOW",
      "initial_rms_ka": 8.962416883591409,
      "source_fault_sha256": "8c1aa687727b9c0af9bd6622178d9361eabe8f305c120a5ec171b6c073bfaffc",
      "duty_settings_sha256": "9ef15e3a8d2026e1a5275642814438d4b610c665af102fd496273f8345bf0a34",
      "clearing_seconds": 0.07967639790006337,
      "screening_ka2_seconds": 6.3999999999999995,
      "withstand_ka2_seconds": 10.0,
      "status": "below_rating",
      "thermal_margin_ka2_seconds": 3.6000000000000005,
      "constant_initial_rms_duration_at_rating_s": 0.12449437171884903,
      "scope": "Assumes constant RMS current until clearing. Interrupting current and decay are outside scope."
    },
    "duty_reference_scope": "Bolted-fault screen only. Arcing-current clearing time requires a separate assessment.",
    "arcing_clearance": {
      "scope": "Supplied arcing currents and total clearing-time band",
      "device_id": "SYNTHETIC",
      "curve_source": "Synthetic regression fixture",
      "input_sha256": "4451df64df57556b83000facac0c9102be7c2826cab8e877be17354463a29164",
      "cases": {
        "nominal": {
          "arcing_current_ka": 8,
          "earliest_seconds": 0.05,
          "latest_seconds": 0.1,
          "status": "covered"
        },
        "reduced": {
          "arcing_current_ka": 4,
          "earliest_seconds": 0.1,
          "latest_seconds": 0.2,
          "status": "covered"
        }
      },
      "longest_latest_seconds": 0.2,
      "longest_clearing_case_ids": [
        "reduced"
      ],
      "status": "covered"
    },
    "study_input_sha256": "53026846e2a23f03dc6686efad2245a3c9973ac040859a0e791a3f4da1533006",
    "handoff_input_sha256": "192d7aa5fc5b67fdc9f2ad2a45782adb4d108dffc342b80b17a553e30e570aaf",
    "incident_energy_review": {
      "scope": "Comparison of supplied incident-energy results",
      "source": "Synthetic fixture",
      "study_input_sha256": "53026846e2a23f03dc6686efad2245a3c9973ac040859a0e791a3f4da1533006",
      "report_sha256": "2726b979228b08bdec9d57979cf0a6e671b75efeed10c97214d32dce539e057a",
      "clearing_input_sha256": "4451df64df57556b83000facac0c9102be7c2826cab8e877be17354463a29164",
      "clearing_device_id": "SYNTHETIC",
      "clearing_curve_source": "Synthetic regression fixture",
      "cases": {
        "nominal": {
          "arcing_current_ka": 8,
          "earliest_seconds": 0.05,
          "latest_seconds": 0.1,
          "status": "covered",
          "incident_energy_cal_per_cm2": 6
        },
        "reduced": {
          "arcing_current_ka": 4,
          "earliest_seconds": 0.1,
          "latest_seconds": 0.2,
          "status": "covered",
          "incident_energy_cal_per_cm2": 4
        }
      },
      "maximum_cal_per_cm2": 6,
      "maximum_case_ids": [
        "nominal"
      ]
    }
  },
  "boundary_review": {
    "scope": "Comparison of supplied incident-energy results",
    "source": "Synthetic fixture",
    "study_input_sha256": "53026846e2a23f03dc6686efad2245a3c9973ac040859a0e791a3f4da1533006",
    "report_sha256": "bf786f5a6c0ab099fe0ba4b4c6d3086c1eca94c3b69cf616f29cabca69f0adff",
    "clearing_input_sha256": "4451df64df57556b83000facac0c9102be7c2826cab8e877be17354463a29164",
    "clearing_device_id": "SYNTHETIC",
    "clearing_curve_source": "Synthetic regression fixture",
    "cases": {
      "nominal": {
        "arcing_current_ka": 8,
        "earliest_seconds": 0.05,
        "latest_seconds": 0.1,
        "status": "covered",
        "incident_energy_cal_per_cm2": 6,
        "arc_flash_boundary_mm": 930
      },
      "reduced": {
        "arcing_current_ka": 4,
        "earliest_seconds": 0.1,
        "latest_seconds": 0.2,
        "status": "covered",
        "incident_energy_cal_per_cm2": 4,
        "arc_flash_boundary_mm": 1050
      }
    },
    "maximum_cal_per_cm2": 6,
    "maximum_boundary_mm": 1050,
    "maximum_boundary_case_ids": [
      "reduced"
    ],
    "maximum_case_ids": [
      "nominal"
    ]
  },
  "incident_energy_tie": {
    "scope": "Comparison of supplied incident-energy results",
    "source": "Synthetic fixture",
    "study_input_sha256": "53026846e2a23f03dc6686efad2245a3c9973ac040859a0e791a3f4da1533006",
    "report_sha256": "fd4148e0e6934efe652fe68cf8d9e72520317f82fdca5816759a24aae72769d2",
    "clearing_input_sha256": "4451df64df57556b83000facac0c9102be7c2826cab8e877be17354463a29164",
    "clearing_device_id": "SYNTHETIC",
    "clearing_curve_source": "Synthetic regression fixture",
    "cases": {
      "nominal": {
        "arcing_current_ka": 8,
        "earliest_seconds": 0.05,
        "latest_seconds": 0.1,
        "status": "covered",
        "incident_energy_cal_per_cm2": 6
      },
      "reduced": {
        "arcing_current_ka": 4,
        "earliest_seconds": 0.1,
        "latest_seconds": 0.2,
        "status": "covered",
        "incident_energy_cal_per_cm2": 6
      }
    },
    "maximum_cal_per_cm2": 6,
    "maximum_case_ids": [
      "nominal",
      "reduced"
    ]
  },
  "incomplete_arcing_coverage": {
    "scope": "Supplied arcing currents and total clearing-time band",
    "device_id": "SYNTHETIC",
    "curve_source": "Synthetic regression fixture",
    "input_sha256": "e7d68f575e51b5fee28cc8000eda5d81bbadb9abcad2bf35c9cec06420c7ab6d",
    "cases": {
      "nominal": {
        "arcing_current_ka": 8,
        "earliest_seconds": 0.05,
        "latest_seconds": 0.1,
        "status": "covered"
      },
      "reduced": {
        "arcing_current_ka": 1,
        "earliest_seconds": null,
        "latest_seconds": null,
        "status": "outside_curve"
      }
    },
    "longest_latest_seconds": null,
    "longest_clearing_case_ids": [],
    "status": "incomplete_coverage"
  }
}